Presence Detection Settings
Presence Detection
possible values: Yes / No
default: No
Global Presence Detection (PD) functionality enable/disable. Further information can be found in section Presence Detection.
Use Only Presence Anchors
possible values: Yes / No
default: No
if set to Yes, only anchors explicitly set in "Presence" localization mode are used for Presence Detection. If set to No, then also anchors set in "True Location" mode can report position using PD. The anchor configured in the “True Location” mode calculates the position using PD mode only if it is not possible to calculate the "True Location" position and after the "Minimal Time to Trigger" has elapsed.
Minimal Time to Trigger
possible values: range from 0 to 65535 milliseconds
default: 5000
The hysteresis in milliseconds to switch from True Location mode to Presence Detection mode. By setting the value of 0, the tag will immediately report PD position as soon as it is impossible to calculate the precise position. Thanks to this parameter, one can prevent frequent jumps because of alternation between True Location and Presence Detection mode. This might look like erratically jumps from precise position to position of any anchor.
Rxpowerlevel Threshold
possible values: number in range from -115 to -75
default: -85
Only anchors that have received a blink with RSSI better than this parameter can be used to determine PD position. This makes it possible to limit the distance to which PD is activated - RSSI values less than -80 are mostly in the immediate vicinity of the anchor.
Threshold To Switch Anchors
possible values: number in range from 0 to 40
default: 5
The tag changes its PD position only if the RSSI on the second anchor is improved by at least that value. As a result, the stability of the PD position will increase, and the tag will not jump once it is within the range of two anchors.